SENSORWORX power pack controllers transform incoming line voltage power to Class 2 low voltage as needed by sensors or other control devices. Additionally, they switch on/off power to the connected lighting load as directed by the sensors and controls. SENSORWORX power packs utilize a powerful microprocessor to optimize its switching timing in order to ensure long relay life even when controlling high-inrush LEDs and ballast loads. As with all SENSORWORX products, these power packs are easy to install and incorporate features which reduce contractor labor time. An elongated chase nipple with snaps for quick installation and an optional snap-on low voltage wire chamber make for a hassle free contractor experience. All SENSORWORX products are proudly made in the USA.
Basic Operation
An input signal indicating occupancy from one or more connected sensors will signal the pack’s integrated relay to close. Once closed, line voltage will flow through the relay and turn on the connected lighting load. When the input signal indicates the occupied period has ended, the relay will open and lighting will switch off. This pack is also available with an auxiliary switch input to enable manual on, hold on, and hold off configurations.
Applications
-
Classrooms
-
Copy Rooms
-
Open Areas
-
Small Offices
-
Conference Rooms
-
Private Restrooms
-
Hallways
Features / Power Pack Controller (347)
-
Powers Low Voltage Sensors
-
Switches Line Voltage Loads
-
Electronically Timed Switching (i.e. Zero Crossing) Ensures Long Relay Life
-
Integrated Test/Programming Button
-
Plenum Rated (UL 2043)
-
Optional Snap-On Attachment Provides Chamber for Low Voltage Wire Connections
-
Optional Switch Input for Manual On, Hold On, or Hold Off Operation
Specifications
Physical
SIZE
3.00” H x 2.25” W x 1.88” D
(7.62 cm x 5.72 cm x 4.78 cm)
WEIGHT
6.00 oz.
COLOR
Blue
MOUNTING
1/2” Knockout
RELAY TEST BUTTON
LED STATUS INDICATOR
Bi-color White & Blue
Environmental
OPERATING TEMP
32°F to 122°F (0°C to 50°C) Std.
-40° F/C (with -HE Option)
RELATIVE HUMIDITY
0-95% Non-Condensing, Indoor Use Only
ROHS COMPLIANT
Electrical
OPERATING VOLTAGE
120/347 VAC
CLASS 2 OUTPUT RATINGS
Output capacity: 18 VDC, 150 mA
Output power for connected devices:
80 mA
Power draw if not connected to
120/347 VAC: 70 mA
AC LOAD RATINGS
relay uses zero-cross switching
20A @ 120 VAC – General Purpose Plug Load
20A @ 120/347 VAC – General Purpose, Tungsten Magnetic Ballast
16A @ 120/347 VAC – Electronic Ballast, LED Driver
DC LOAD RATINGS
20A @ 28 VDC (MAX) 1A @ 5 VDC (MIN)
MOTOR LOAD
1 HP
Wiring Diagrams
Basic Sensor Wiring – SWX-903
Basic Sensor Wiring – SWX-903-AX
Common Sensor Configurations – Single Sensor
Common Sensor Configurations – Multiple Sensor
Multiple Power Packs with Common Line Feeds
Multiple Power Packs with Separate Line Feeds
Power Packs with Secondary Relay Pack
Power Pack Connected to Switch – Momentary Switch (Requires –AX Option)
- Some energy codes require Manual On (also called Vacancy) operation where an occupant is required to initially switch on lighting. The sensor then ensures lights are turned off once the space is unoccupied
- Interfacing momentary switches such as the SWX-801-xx or SWX-803-xx are recommended, however maintained switches can also be utilized
- For momentary switches, the power pack will react on the leading edge of a pulse on the brown input wire
- For maintained switches, any change of state on the brown wire that lasts longer than 0.5 seconds will be read by the power pack as one action
- If no sensor is present, tie power pack low voltage white wire to low voltage red wire
Power Pack Connected to Switch – Maintained Switch (Requires –AX Option)
- Some energy codes require Manual On (also called Vacancy) operation where an occupant is required to initially switch on lighting. The sensor then ensures lights are turned off once the space is unoccupied
- Interfacing momentary switches such as the SWX-801-xx or SWX-803-xx are recommended, however maintained switches can also be utilized
- For momentary switches, the power pack will react on the leading edge of a pulse on the brown input wire
- For maintained switches, any change of state on the brown wire that lasts longer than 0.5 seconds will be read by the power pack as one action
- If no sensor is present, tie power pack low voltage white wire to low voltage red wire
Power Pack with Switch Signal from External System
-
Typical for Hold On and Hold Off applications
-
BROWN switch input can be activated by external signals +5VDC or higher (i.e. logic high)
-
For hold on and hold off applications, switch input can also be configured to activate on logic low
-
If no sensor is present, tie power pack low voltage white wire to low voltage red wire
Multi-Way Switching (Requires -AX Option)
- Switching a powerpack from multiple locations (i.e., 3-way, 4-way switching) can be achieved using multiple SENSORWORX model# SWX-801-xx switches or a combination of one model# SWX-803-xx dimmer and one or more model# SWX-801-xx switches.
- Note that only one dimmer should be used per multi-way application.
- If no sensor is present, tie power pack low voltage white wire to low voltage red wire
Installation Options
Ordering Info
EXAMPLE MODEL # SWX-903-AX
| PRODUCT | FUNCTIONALITY | VOLTAGE | AUX SWITCH INPUT | ADDITIONAL OPTIONS | ||||||
|---|---|---|---|---|---|---|---|---|---|---|
| SWX– | Power Pack | 9 | Single Relay + 150 mA Supply | 0 | 120/347 VAC | 3 | None | Blank | High Humidity Environment | -HE |
| Auxiliary Switch Input | –AX |
| ACCESSORY | DESCRIPTION |
|---|---|
| SWX-999 | Snap-On Low Voltage Wiring Chamber |
Compatible Wireless Products
Wireless Dimmer & Switch
These stylish and intuitive wall stations are designed for a 10 year battery life.
Wireless Ceiling Sensors
Available with either PIR and Dual Tech. occupancy detection, these wireless sensors can be paired with a load controller in seconds.
Wireless Wide View Sensors
With five contractor friendly mounting methods, locating a sensor in a corner has never been easier.