Wide View Sensors

SWX-400 SERIES

Overview

The SENSORWORX wide view occupancy sensor enables mounting to a wall, corner, junction box, or conduit. This flexibility reduces contractor installation time and provides a secure and clean finished appearance. SENSORWORX products utilize the latest passive infrared technology and digital signal processing techniques to provide unmatched detection performance. Additionally, these SENSORWORX units are available with an integrated microphone to provide overlapping passive acoustic occupancy detection for rooms with obstructions or where occupant motion will be limited.

 

Basic Operations

Sensors detect movement in the infrared energy that radiates from occupants as they move within the devices field-of-view. Once occupancy is identified the sensor signals a connected power/relay pack to switch on the connected lighting. If equipped with passive dual (PIR/Acoustic) technology, the unit’s microphone is then also enabled to further enhance detection while the lights are on. An internal timer is set to keep lights on during brief periods of inactivity and is reset every time occupancy is signaled by either the passive infrared or acoustic detection technologies.

Applications

A single wide view sensor can be used in many rooms, however, multiple low voltage sensors can be easily wired together to provide improved coverage for large or irregular shaped spaces.

  • Classrooms
  • Open Areas
  • Large Offices
  • Conference Rooms
  • Hallways

Features / Wide View Sensors

  • Digital Passive Infrared (PIR) Detection
  • 120° Coverage Pattern
  • Convenient Test Mode and Adjustable Time Delays
  • Passive Acoustic Detection (Optional)
  • Five Contractor Friendly Mounting Methods
  • Compact Size and Matte Finish
  • Mounting Nipple Attachment with Integrated Hole Saw

Specifications

Physical

SIZE
2.875” H x 2.75” W x 3.25”D
(7.30 x 6.98 x 8.25 cm)

WEIGHT
4.75 oz.

COLOR
White

Environmental

OPERATING TEMP
-10°F to 122°F (14°C to 50°C)

RELATIVE HUMIDITY
0-95% Non-Condensing, Indoor Use Only

ROHS COMPLIANT

Electrical

OPERATING VOLTAGE

12-24 VAC/VDC

CURRENT DRAW

4mA

OUTPUT
Logic High VDC (Occupied Mode)

RECOMMENDED POWER PACKS
SENSORWORX (e.g., SWX-900)

Operation

TIME DELAYS
0 sec. to 30 min.
10 Minute Default

TEST MODE
5 sec.

Coverage Patterns

Wide View 120°

MOUNTING HEIGHT
8 to 12 ft (2.44 to 3.66 m)

SMALL MOTION DETECTION 
Up to 40 ft (12.19 m)
(e.g. Hand Movements)

LARGE MOTION DETECTION
Up to 70 ft (21.34 m)
Perfect for Hallway Applications
(e.g. Walking)

Wiring Diagrams

Low Voltage

ELECTRICIAN FRIENDLY DESIGN
Class 2 Wiring Direct to Power Pack

RECOMMENDED POWER PACK
SENSORWORX SWX-900

Installation Options

Ordering Info

EXAMPLE MODEL # SWX-421-1
 PRODUCT DETECTION COVERAGE VOLTAGE 
SWXWide View Sensor4Passive Infrared (PIR)0120° Wide View1Low Voltage1
Passive Dual Technology (PIR/Acoustic)2

Wide View Sensors Popular Model Numbers

SWX-401-1Passive Infrared (PIR) | 120° Wide View | Low Voltage
SWX-421-1Passive Dual Technology (PIR/Acoustic) | 120° Wide View° | Low Voltage

Related Products

Wall Switch Sensors

This wall switch sensor is significantly shallower than typical sensors, resulting in less crowded wall boxes.

Ceiling Sensors

This sensor’s chase nipple attachment makes surface mounting to a finished ceiling simple and secure.

Power Packs

Mounting snaps and an optional low voltage wiring chamber make this power pack a breeze to install.

Design by DZYNR | ©2018 BLP Technologies, Inc. All Rights Reserved.